@@ -50,21 +50,37 @@ using (var disposables = new CompositeDisposable())
the best way to test your PLC application is running your [SoftPLC](https://github.com/fbarresi/softplc) locally.
## S7 Addressing rules
## Addressing rules
Sharp7Reactive uses a syntax for identifying addresses similar to official siemens syntax.
Every address has the form (case unsensible) `DB<number>.<TYPE><Start>.<Length/Position>`.
<br/>i.e.: `DB42.DBX0.7` => (means) Datablock 42, bit (DBX), Start: 0, Position: 7
<br/>or<br/>
`DB42.DBB4.25` => (means) Datablock 42, bytes (DBB), Start: 4, Length: 25.
Every address has the form (case unsensitive) `DB<number>.<TYPE><Start>.<Length/Position>`.
Following types are supported:
- `DBX` => Bit (bool)
- `DBB` => byte or byte[]
- `INT`
- `DINT`
- `DUL` => LINT
- `D` => REAL
| Example | Explaination |
| ------------------------------------ | ----------------------------------------------------------------- |
| `DB42.Int4` or<br> `DB42.DBD4` | Datablock 42, 16 bit integer from bytes 4 to 5 (zero based index) |
| `DB42.Bit0.7` or<br>`DB42.DBX0.7` | Datablock 42, bit from byte 0, position 7 |
| `DB42.Byte4.25` or<br>`DB42.DBB4.25` | Datablock 42, 25 bytes from byte 4 to 29 (zero based index) |
Here is a table of supported data types:
|.Net Type|Identifier |Description |Length or bit |Example |Example remark |
|---------|-----------------------------|----------------------------------------------|----------------------------------------|-------------------|--------------------------|
|bool |bit, dbx |Bit as boolean value |Bit index (0 .. 7) |`Db200.Bit2.2` |Reads bit 3 |
|byte |byte, dbb, b* |8 bit unsigned integer | |`Db200.Byte4` | |
|byte[] |byte, dbb, b* |Array of bytes |Array length in bytes |`Db200.Byte4.16` | |
|short |int, dbw, w* |16 bit signed integer | |`Db200.Int4` | |
|ushort |uint |16 bit unsigned integer | |`Db200.UInt4` | |
|int |dint, dbd |32 bit signed integer | |`Db200.DInt4` | |
|uint |udint |32 bit unsigned integer | |`Db200.UDInt4` | |
|long |lint |64 bit signed integer | |`Db200.LInt4` | |
|ulong |ulint, dul*, dulint*, dulong*|64 bit unsigned integer | |`Db200.ULInt4` | |
|float |real, d* |32 bit float | |`Db200.Real4` | |
|double |lreal |64 bit float | |`Db200.LReal4` | |
|string |string, s* |ASCII text string with string size |String length in bytes (1 .. 254) |`Db200.String4.16` |Uses 18 bytes = 16 + 2 |
|string |wstring |UTF-16 Big Endian text string with string size|String length in characters (1 .. 16382)|`Db200.WString4.16`|Uses 36 bytes = 16 * 2 + 4|
|string |byte[] |ASCII string as byte array |String length in bytes |`Db200.Byte4.16` |Uses 16 bytes |
> Identifiers marked with * are kept for compatability reasons and might be removed in the future.
## Would you like to contribute?